Outline

Ingegneria Sismica

Ingegneria Sismica

Research on the Influence of Wireless Power Transmission on the Insulation Performance of Power Safety Tools

Author(s): Rongfu He1, Peng Li1, Junyi Zhu1, Shici Gu2, Hui Jia1, Huan Liu1
1State Grid Jibei Electric Power Limited Smart Distribution Network Center, Qinhuangdao, 066100, China
2State Grid Jibei Electric Power Company Limited, Beijing, 100031, China
He, Rongfu. et al “Research on the Influence of Wireless Power Transmission on the Insulation Performance of Power Safety Tools.” Ingegneria Sismica Volume 43 Issue 3: 1-21, doi:10.65102/is20261164.

Abstract

With the rapid promotion of wireless power transmission technology (WPT) in the fields of electric transportation, smart devices, and medical implants, it poses new engineering challenges to the insulation performance of power safety tools. This study systematically evaluated the synergistic aging effect of composite electromagnetic fields of power frequency and wireless power transmission on the electrical thermal microstructural properties of solid insulation materials. A multidimensional measurement index system was constructed based on standards such as ASTM D257, IEC 60250, and IEC 60243, combined with DSC, TGA, SEM/EDS, and partial discharge testing; The performance attenuation law under different frequencies, field strengths, and material combinations was investigated through orthogonal experiments and control group design. The results indicate that high-frequency excitation in the WPT frequency band significantly accelerates the increase of dielectric loss factor and the decrease of partial discharge initiation voltage, and the frequency dependence is closely related to the microstructure of the material; The thermal electric coupling effect generated under composite field loading further exacerbates the formation of material microcracks and surface electrical traces. The research results of this article provide theoretical and experimental basis for the reliability prediction of power safety tools in WPT environment.

Keywords
Wireless Power Transfer; Solid Insulation Materials; Composite Electromagnetic Field; Dielectric Loss Mechanism; Aging Evaluation Framework

Related Articles

Qianwen Xiong1, Yuhong Chen1
1Guangzhou University of Chinese Medicine, School of Pharmaceutical Medicine, Guangzhou,Guangdong,China,510006
Zhihao Jiang1,2, Limi Chen1,2, Jing Yang1
1Hainan Vocational University of Science and Technology, Haikou 571126, China
2Institute for Mathematical Research, Universiti Putra Malaysia, Serdang 43400, Malaysia
Limi Chen1,2, Zhihao Jiang1,2, Jing Yang1
1Hainan Vocational University of Science and Technology, Haikou 571126, China
2Institute for Mathematical Research, Universiti Putra Malaysia, Serdang 43400, Malaysia
Hui Yuan1, Minjie Chai2, Siqing Xu1, Jinsong Li1, Jinwan Zheng1
1Electric Power Research Institute, State Grid Shanxi Electric Power Co., Ltd., Taiyuan, 030001, Shanxi, China
2Jincheng Power Supply Branch, State Grid Shanxi Electric Power Co., Ltd., Jincheng, 048000, Shanxi, China
Yanhan Zhu1,2
1China Academy of Cultural Heritage, Chaoyang District, 100029, Beijing, China
2Beijing University of Civil Engineering and Architecture, Xicheng District, 100044, Beijing, China